Click for Rapid City, South Dakota Forecast

mitsubishi logo

Diesel Industrial Standby and Prime Power

Powerdak Generators with Diesel Engines by Mitsubishi

 

MITSUBISHI is one of the world's leading manufacturers of diesel engines. Our Powerdak Mitsubishi driven generator line is full of standard features and ready to deliver the power you need!

 

For More Information please call 888-861-8984 or 605-341-6160 Ext 1

 

For your convenience, Powerdak offers a specification comparrison chart below.

For complete specifications, please refer to the PDF file. 

Mitsubishi Comparrison Chart

800-2000kWe

 powerdak power products llc logo 3 MD800
800/735 kWe
208-600 Volt
60 Hz / 1800 RPM
Standby/Prime
MD1000
1000/920 kWe
208-600 Volt
60 Hz / 1800 RPM
Standby/Prime
MD1250
1250/1150 kWe
208-600 Volt
60 Hz / 1800 RPM
Standby/Prime
MD1600
1600/1450 kWe
208-600 Volt
60 Hz / 1800 RPM
Standby/Prime
MD2000
2000/1850 kWe
2
08-600 Volt
60 Hz / 1800 RPM
Standby/Prime
COMPARISON CHART pdf logo pdf logo pdf logo pdf logo pdf logo
kWe (Stby/Prime) 800 / 735 1000 / 920 1250/ 1150 1600 / 1450 2000 / 1850
AMPS (Stby/Prime)
240V (Phase 1)
208V (Phase 3)
240V (Phase 3)
480V (Phase 3)
600V (Phase 3)

N/A
2779 / 2553
2408 / 2213
1204/ 1106
963 / 885

N/A
3474 / 3196
3011 / 2770
1505 / 1385
1204 / 1108

N/A
4342 / 3995
3763 / 3462
1881 / 1731
1505 / 1385

N/A
5558 / 5037
4817 / 4365
2408 / 2183
1927 / 1746

N/A
6948 / 6426
6021 / 5569
3011 / 2785
2408 / 2228
ENGINE
Manufacturer:
Type:
Aspiration:
Arrangment:
Max HP Stby:

Mitsubishi
4 Cycle
Turbo Charged
12 Cylinder Vee
1207

Mitsubishi
4 Cycle
Turbo Charged
12 Cylinder Vee
1528

Mitsubishi
4 Cycle
Turbo Charged
12 Cylinder Vee
1881

Mitsubishi
4 Cycle
Turbo Charged
16 Cylinder Vee
2346

Mistubishi
4 Cycle
Turbo Charged
16 Cylinder Vee
2923

FUEL CONSUMPTION

(gal/hr) (Stby/Prime)
100%
75%
50%

 

 

67.4 / 58.7
46.1 / 42.0
31.3 / 28.6

 

 

75.0 / 70.2
59.7 / 54.6
39.8 / 36.0

 

 

103 /91.0
75.1 / 68.4
51.0 / 46.4

 

 

129.2 / 115.4
94.1 / 86.8
64.4 / 58.7

 

 

160.1 / 141.5
116.7 / 106.6
79.0 / 71.7

FLUID CAPACITY

(gal/hr) (Stby/Prime
Total Oil System:
Engine Jacket Water Capaciity:
System Coolant Capacity:

 

 

31.7 / 31.7
26.4 / 26.4
80.0 / 80.0

 

 

52.8 / 52.8
26.4 / 26.4
84.0 / 84.0

 

 

39.6 / 39.6
34.3 / 34.3
86.0 / 86.0

 

 

52.8 / 52.8
44.9 / 44.9
97.0 / 97.0

 

 

52.8 / 52.8
44.9 / 44.9
104 / 104

WEIGHT

(Pounds)
OPU:
Level 1:
LeOPU:vel 2:
Level 3:

 

 

16750
18850
N/A
21000

 

 

20550
22650
N/A
24800

 

 

23575
29900
N/A
34750

 

 

30150
35850
N/A
CF

 

 

32200
39000
N/A
CF

DIMENSIONS

(Inches) (LxWxH)
OPU:
Level 1:
Level 2:
Level 3:

 

 

180x75x95
200x90x108
N/A
344x90x108

 

 

180x62x81
2002x100
N/A
344x90x108

 

 

220x96x112
240x106x129
N/A
420x106x129

 

 

250x94x119
265x110x135
N/A
CF

 

 

255x110x130
265x110x145
N/A
CF

NOISE OUTPUT

(dBA)(No Load/Full Load)
OPU:
Level 1:
Level 2:
Level 3:

 

 

87 / 90
86 / 88
N/A
74 / 78

 

 

87 / 90
86 / 88
N/A
75 / 79

 

 

89 / 92
87 / 90
N/A
79 / 81

 

 

90 / 92
88 / 91
N/A
CF

 

 

91 / 95
90 / 94
N/A
CF
 
Aspirating: CFM (m³/min)
3,602 (102)
3,284 (92.9)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
47,973 (1,358)
47,973 (1,358)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Consult Factory For Remote Cooled Applications